IP Radio Unit for Modbus

IP Gateway for Remote Control with ModBus, Designed for Modern Energy Providers

IP Radio Unit for Modbus
southDownload product sheet
PDF(1207KB)

check mark

2 LAN Interfaces

check mark

Integrated TETRA Communication Module

check mark

RS485 / ModBus Protocol Support

check mark

Suitable for DIN Mounting Frames

check mark

Integrated Config Web Server

check mark

Centralized Config & Management

Technical specification

Technical specifications
Power supplyConnector: MULTICOMP 2MJ-0402A120
Voltage: 12–24V DC
Consumption: 15W
Ethernet port2 x RJ45 10Mbps and 100Mbps with auto negotiation (side)
Antenna connectorFME male (50Ω), supporting TETRA frequency bands 380–400MHz and 410–430MHz
Service portUSB-C
Reset buttonReset to factory defaults
LED indicatorsPower, LAN, Radio Status, Radio Rx, Radio Tx, RS485 (Rx, Tx, Error)
Main connectors4 x Phoenix SPT-THR 1,5/ 8-V-5,0
Digital I/O8 x digital inputs
4 x digital outputs (relays)
RS485 interface1 x pair connection (RS485RD+ RS485RD-)
2 x pair connection (RS485RD+ RS485RD-, RS485TD+ RS485TD-)
RS485 GND (communication cable shield – when necessary)
MountingDIN rail
Dimensions (HxWxD)175 x 105 x 55mm
Weight700g
Operating temperature-5°C to +60°C
Storage temperature-25°C to +70°C
EMCEN 55032 kl. A:2015 + A11:2020 + A11:2020
EN IEC 61000-6-2:2019
EN 55035:2017 + A11:2020
EN 301 489-1 V2.2.3

Related solutions